iRidium for TIS
a set of tools to create control interfaces for equipment in the TIS.
The documentation was updated on 26.9.2023
Connection
There are various ways of communicating with the bus, allowing you to work locally and over the Internet if you have a static IP address or a dynamic IP address:
Local Mode
The "Local" mode works only in the local network and it does not allow you to set up control of the bus via the Internet. A broadcast address is used for connection. Local connection works with any IP device by TIS.
TIS Remote Server
TIS Remote Server allows to connect to IP-gateway by TIS via internet in case you do not have a static IP-address or a domain (DDNS). Connection is set via the internet servers by TIS that are used for authorization between iRidium control panel and TIS IP-interface.
Serial
The Serial protocol supports connection via standard Serial port such as COM1 in Windows or /dev/ser1 in QNX. To work with the equipment, enter the «remote» host or a device with which the connection is performed.
Connection Settings
Local Mode
The "Local" mode works only in the local network and it does not allow you to set up control of the bus via the Internet. A broadcast address is used for connection. Local connection works with any IP gateway by TIS.
If Fixed IP mode in turned on in the settings of TIS IP gateway, enter data to work in the local network
- IP Address - local IP-address of TIS module;
- Mask - subnet mask;
- Gateway - gateway by default.
Enter a local address to connect to TIS IP-gateway in the settings of the TIS Network driver. If it is recommended by the system admin, change the broadcast address, otherwise leave the setting by default.
- Connect type: Local – mode of local connection to TIS IP-module;
- Host – broadcasts address to exchange data with TIS;
- Port - connection port (by default it is 6000).
TIS Remote Server Mode
TIS Remote Server allows to connect to IP-gateway by TIS via internet in case you do not have a static IP-address or a domain (DDNS). Connection is set via the internet servers by TIS that are used for authorization between iRidium control panel and TIS IP-interface.
You can find addresses of available remote TIS servers in TIS DevSearch. Go to Network Configuration window and have a look at Server IP Address line. They can also be found in the settings of IP-interface.
Enter a required TIS server and its connections password in the IPPort Parameters section in the settings of the IP gateway. Hold the programming button on the device for 7 seconds. After it the device goes into the programming mode. Save the settings in the app and press a button on the device to leave the programming mode and reset the device.
Enter connection parameters to TIS IP gateway via a remote server in the settings of the TIS Network (UDP) driver;
- Host - address of a remote server TIS(Server IP Address). Enter the address of the TIS remote server that is set in the IP gateway;
- Port - port to connect to the IP gateway via a remote server. It's the same as in the settings of the IP gateway (by default it is 6000);
- Password - connection login from the settings of IP gateway;
- MAC - МАС-address of TIS IP gateway.
Serial
- Protocol - Serial;
- Log Level - level of logging;
- Used with iRidi device - set the host for the corresponding equipment (if this parameter is selected, the Host line will be inactive);
- Port - connection port.
Work in iRidium
1 Create a new project and add TIS Network driver.
2 Enter connection settings of a driver according to the type of connection Local or TIS Remote Server. You'll find detailed information about connection settings in the Connection setting section.
3 Click left mouse button on the added TIS Network driver and add required devices. Each device has a preset list of commands and feedback channels according to its type.
Fill in settings for each device to work:
- Subnet ID - subnet ID of the device;
- Device ID - device ID in the subnet;
- Device Type - type of device. Depending on the type of a device a definite list of "Operation Code" is available.
Setting Commands and Feedback Channels
To control equipment it is required to set commands (Commands) and feedback channels (Feedbacks). To send a command, drag'n'drop it on a graphic item and enter a value to send. To display feedback drag'n'drop a feedback channel on a graphic item and choose how to output or display a value.
Read more about work with graphic items in the
"Types of graphic items" article.
In the TIS Network driver, each device has a set of Operation Codes specific to their type. Also, for the convenience of users, a Custom device has been added, where you can endow it with a unique set of Operation Code.
Air conditioner
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read the temperature unit |
It sends a request to get the temperature.
|
| Value* |
any value |
It gets any value to activate a command.
|
| Operation Code |
Read air condition Fan speed and Mode En/Dis Flag |
It sends a request to get the fan mode.
|
| AC |
1...n |
The number of a thermostat.
|
| Mode |
Fan Auto, Fan High, Fan Med, Fan Low, Climate Cool, Climate Heat, Climate Fan, Climate Auto, Climate Dry. |
The mode of thermostat work.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read air condition temperature range |
It sends a request to get the temperature range of a conditioner.
|
| AC |
1...n |
The number of a thermostat.
|
| Temperature parameter |
Cool Low, Cool High, Heat Low, Heat High, Auto Low, Auto High, Dry Low, Dry High |
A temperature mode.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Set the parameters of the air conditioner |
It sets the parameters of conditioning.
|
| AC |
1...n |
The number of a thermostat.
|
| AC parameter |
OnOff, Cool temperature, Mode, Speed, Heat temperature, Auto temperature, Dry temperature. |
Parameters to control a thermostat.
|
| Value * |
0 - turn off, 1 - turn on |
OnOff
|
| 15-30 |
Cool temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Mode
|
| 0-3 (Auto, High, Med, Low) |
Speed
|
| 1...n |
Room temperature
|
| 15-35 |
Heat temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Current mode
|
| 0-3 (Auto, High, Med, Low) |
Current speed
|
| 15-35 |
Auto temperature
|
| 15-35 |
Dry temperature
|
| Operation Code |
Read the parameters of the air condition |
It sends a request to get the parameters of air-conditioning.
|
| AC |
1...n |
The number of a thermostat.
|
| AC parameter |
OnOff, Cool temperature, Mode, Speed, Heat temperature, Auto temperature, Dry temperature. |
Parameters to control a thermostat.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Set the parameters of thermostat |
It sets the parameters of a thermostat.
|
| Command |
AC1, AC1 Cool temperature, AC1 Fan speed, AC1 Mode, AC1 Heat temperature, AC1 Auto temperature, Floor Heater, Floor temperature, Floor Heater 1, Floor Heater 2, Floor Heater all. |
Selection of a parameter.
|
| Value* |
On, Off |
AC1
|
| 15 ~ 30 |
AC1 Cool temperature
|
| Auto, High, Med, Low |
AC1 Fan speed
|
| Auto, Cool, Heat, Fan |
AC1 Mode
|
| 15 ~ 35 |
AC1 Heat temperature
|
| 15 ~ 35 |
AC1 Auto temperature
|
| On, Off |
Floor Heater
|
| 15 ~ 35 |
Floor temperature
|
On, Off, Temperature (15 ~ 35) |
Floor Heater 1
|
On, Off, Temperature (15 ~ 35) |
Floor Heater 2
|
On, Off, Temperature (15 ~ 35) |
Floor Heater all
|
| Operation Code |
Read the parameters of thermostat |
It sends a request to get parameters of a thermostat.
|
| Action type |
On/Off |
It gets information about the state of a thermostat (on or off).
|
| Temperature |
It gets the temperature of a thermostat
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Read the temperature unit |
The value of temperature.
|
| Value * |
n |
Temperature.
|
| Operation Code |
Read air condition Fan speed and Mode En/Dis Flag |
The value of a fan mode.
|
| AC |
1...n |
The number of a conditioner.
|
| Mode |
Fan Auto, Fan Med, Fan Height, Fan Low, Climate Cool, Climate Heat, Climate Fan, Climate Auto, Climate Dry. |
The mode of a conditioner.
|
| Value * |
0 |
Turned off.
|
| 1 |
Turned on.
|
| Operation Code |
Read air condition temperature range |
Temperature range.
|
| AC |
1...n |
The number of a conditioner.
|
| Temperature parameter |
Cool Low, Cool High, Heat Low, Heat High, Auto Low, Auto High, Dry Low, Dry High. |
Temperature parameter.
|
| Value * |
15-30 |
Cool Low
|
| 15-30 |
Cool High
|
| 15-35 |
Heat Low
|
| 15-35 |
Heat High
|
| 15-35 |
Auto Low
|
| 15-35 |
Auto High
|
| 15-35 |
Dry Low
|
| 15-35 |
Dry High
|
| Operation Code |
Read the parameters of the air condition |
Conditioner parameters.
|
| AC |
1...n |
The number of a conditioner.
|
| AC parameter |
OnOff, Cool temperature, Mode, Speed, Room temperature, Heat temperature, Current mode, Current speed, Auto temperature, Dry temperature. |
Parameters of a conditioner.
|
| Value * |
0 - turned off, 1 - turned on |
OnOff
|
| 15-30 |
Cool temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Mode
|
| 0-3 (Auto, High, Med, Low) |
Speed
|
| 1...n |
Room temperature
|
| 15-35 |
Heat temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Current mode
|
| 0-3 (Auto, High, Med, Low) |
Current speed
|
| 15-35 |
Auto temperature
|
| 15-35 |
Dry temperature
|
| Operation Code |
Parameters of thermostat |
Parameters of a thermostat.
|
| Command |
AC1, AC1 Cool temperature, AC1 Fan speed, AC1 Mode, AC1 Heat temperature, AC1 Auto temperature, Floor Heater, Floor temperature, Floor Heater 1, Floor Heater 2, Floor Heater all. |
Selection of an air conditioner.
|
| Value* |
1 - On, 0 - Off |
AC1
|
| 15 ~ 30 |
AC1 Cool temperature
|
| 0 ~ 3 (Auto, High, Med, Low) |
AC1 Fan speed
|
| 0 ~ 3 (Auto, Cool, Heat, Fan) |
AC1 Mode
|
| 15 ~ 35 |
AC1 Heat temperature
|
| 15 ~ 35 |
AC1 Auto temperature
|
| 1 - On, 0 - Off |
Floor Heater
|
| 15 ~ 35 |
Floor temperature
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater 1
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater 2
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater all
|
* Value - a value that comes from equipment
Media Control
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read audio source en/disable |
It sends a request to get the status of the sound source (on / off).
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Write audio Source en/disable |
Turn on / off a sound source.
|
| Value* |
0 |
Turn off sound.
|
| 1 |
Turn on sound.
|
| Operation Code |
Write radio station name |
Write the name of a radio station.
|
| Radio station id |
0 - 25 |
The number of a radio station.
|
| Value* |
ASCII |
It accepts a string to write a name.
|
| Operation Code |
Read radio station name |
It sends a request to get the name of a radio station.
|
| Value* |
any value |
It accepts any value to aсtivate a command.
|
| Operation Code |
Read how many album/song In SD/USB |
It sends a request to get the number of albums / songs on a CD / USB.
|
| Directory type |
SD card, USB |
The source of data.
|
| Check type |
Album, Track |
The number of albums / tracks.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Audio command |
It sends an audio command.
|
| Control type |
Music source, Playing mode, Album/radio control, Play control, Volume control |
A type of control.
|
| Music source |
SD card, Audio in 1, FTP Server, FM Radio, Audio in 2. |
Audio source.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Playing mode |
After song stop, Repeat one song, Repeat one album, Repeat album, Randomize. |
Play mode.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Album/radio control |
Previous album, Next album, Specify album, Prev radio channel, Next radio channel, Specify radio no |
Control of audion / albums.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Play control |
Previous song, Next song, Play, Stop. |
Control of playing.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Volume control |
Volume, Treble, Bass |
Sound setting: Decrase, Incrase, Vol value (only for the Volume parameter).
|
| Value* |
0 ~ 79 |
Volume
|
| -7 ~ 7 |
Treble
|
| -7 ~ 7 |
Bass
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Audio sources en/dis |
Audion source (on / off).
|
| Input no |
1...n |
The number of an output.
|
| Value* |
0 |
Turned off.
|
| 1 |
Turned on.
|
| Operation Code |
Radio station name |
The name of a radio station.
|
| Value* |
ASCII |
The name of a radio station.
|
| Operation Code |
Read How Many Album/Song In SD/USB |
The number of albums/songs on a CD/USB.
|
| Value* |
0 ~100 |
The number of albums/songs on a CD/USB..
|
| Operation Code |
Audio command |
Audio command (not realized).
|
| Operation Code |
Media control |
Info about modes of player work.
|
| Control type |
Play/Stop/Pause, Mute, Source, Volume, Effect, Play mode, Channel change, Channel search, Album name, Song name, Play time total, Play time playing, Channel name, Channel frequence. |
A type of command.
|
| Value* |
0 - Play, 1 - Stop, 2 - Pause. |
Play/Stop/Pause.
|
0 - Unmuted, 1 - Muted. |
Mute.
|
1 - SD, 2 - Audio Input 1, 4 - FM, 7 - Audio Input 2, 8 - USB |
Source
|
| 0 ~ 79 |
Volume
|
1 - Normal, 2 - Pop, 3 - Classic, 4 - Jazz, 5 - Rock |
Effect
|
1 - After song stop, 2 - Repeat one song, 3 - Repeat one album, 4 - Repeat album, 5 - Randomize. |
Play mode
|
1 - Previous Channel, 2 - Next Channel |
Channel change
|
| 1...n |
Channel search
|
| ASCII |
Album name
|
| ASCII |
Song name
|
| 1...n |
Play time total
|
| 1...n |
Play time playing
|
| ASCII |
Channel name
|
| 1...n |
Channel frequence
|
* Value - a value that comes from equipment
Audio Matrix MTX-1Z-5S
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read audio source en/disable |
It sends a request to get the status of a sound source (on / off).
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Write audio Source en/disable |
Turn on/ off a sound source.
|
| Value* |
0 |
Turn off sound.
|
| 1 |
Turn on sound.
|
| Operation Code |
Write radio station name |
Write the name of a radio station.
|
| Radio station id |
0 - 25 |
The number of a radio station.
|
| Value* |
ASCII |
It accepts a string to write the name of a radio station.
|
| Operation Code |
Read radio station name |
It sends a request to get the name of a radio station.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read how many album/song In SD/USB |
It sends a request to get the number ot albums / songs on a CD / USB.
|
| Directory type |
SD card, USB |
The source of data.
|
| Check type |
Album, Track |
The number of albums / tracks.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Audio command |
It sends an audio command.
|
| Control type |
Music source, Playing mode, Album/radio control, Play control, Volume control |
A type of control.
|
| Music source |
SD card, Audio in 1, FTP Server, FM Radio, Audio in 2. |
An audio source.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Playing mode |
After song stop, Repeat one song, Repeat one album, Repeat album, Randomize. |
A mode of playing.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Album/radio control |
Previous album, Next album, Specify album, Prev radio channel, Next radio channel, Specify radio no |
Control of radio / albums.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Play control |
Previous song, Next song, Play, Stop. |
Control of playing.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Volume control |
Volume, Treble, Bass |
Sound setting: Decrease, Increase, Vol value (only for the Volume parameter).
|
| Value* |
0 ~ 79 |
Volume
|
| -7 ~ 7 |
Treble
|
| -7 ~ 7 |
Bass
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Audio sources en/dis |
Audio source (on / off).
|
| Value* |
0 |
Turned off.
|
| 1 |
Turned on.
|
| Operation Code |
Radio station name |
The name of a radio station.
|
| Value* |
ASCII |
The name of a radio station.
|
| Operation Code |
Read How Many Album/Song In SD/USB |
The number of albums/songs on a CD/USB.
|
| Value* |
0 ~100 |
The number of albums/songs on a CD/USB.
|
| Operation Code |
Audio command |
An audio command (not realized).
|
| Operation Code |
Media control |
Data about the modes of player work.
|
| Control type |
Play/Stop/Pause, Mute, Source, Volume, Effect, Play mode, Channel change, Channel search, Album name, Song name, Play time total, Play time playing, Channel name, Channel frequence. |
A type of commad.
|
| Value* |
0 - Play, 1 - Stop, 2 - Pause. |
Play/Stop/Pause.
|
0 - Unmuted, 1 - Muted. |
Mute.
|
1 - SD, 2 - Audio Input 1, 4 - FM, 7 - Audio Input 2, 8 - USB |
Source
|
| 0 ~ 79 |
Volume
|
1 - Normal, 2 - Pop, 3 - Classic, 4 - Jazz, 5 - Rock |
Effect
|
1 - After song stop, 2 - Repeat one song, 3 - Repeat one album, 4 - Repeat album, 5 - Randomize. |
Play mode
|
1 - Previous Channel, 2 - Next Channel |
Channel change
|
| 1...n |
Channel search
|
| ASCII |
Album name
|
| ASCII |
Song name
|
| 1...n |
Play time total
|
| 1...n |
Play time playing
|
| ASCII |
Channel name
|
| 1...n |
Channel frequence
|
* Value - a value that comes from equipment
Thermostat
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read the temperature unit |
It sends a request to get the current temperature.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read air condition Fan speed and Mode En/Dis Flag |
It sends a request ot get the fan mode.
|
| AC |
1...n |
The number of a thermostat.
|
| Mode |
Fan Auto, Fan High, Fan Med, Fan Low, Climate Cool, Climate Heat, Climate Fan, Climate Auto, Climate Dry. |
Work modes of a thermostat.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read air condition temperature range |
It sends a request to get the temperature range of a conditiner.
|
| AC |
1...n |
The number of a thermostat.
|
| Temperature parameter |
Cool Low, Cool High, Heat Low, Heat High, Auto Low, Auto High, Dry Low, Dry High |
A temperature mode.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Set the parameters of the air condition |
It sets parameters of air conditioning.
|
| AC |
1...n |
The number of a thermostat.
|
| AC parameter |
OnOff, Cool temperature, Mode, Speed, Heat temperature, Auto temperature, Dry temperature. |
Parameters to control a thermostat.
|
| Value * |
0 - turn off, 1 - turn on |
OnOff
|
| 15-30 |
Cool temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Mode
|
| 0-3 (Auto, High, Med, Low) |
Speed
|
| 1...n |
Room temperature
|
| 15-35 |
Heat temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Current mode
|
| 0-3 (Auto, High, Med, Low) |
Current speed
|
| 15-35 |
Auto temperature
|
| 15-35 |
Dry temperature
|
| Operation Code |
Read the parameters of the air condition |
It sends a request to get the parameters of conditioning.
|
| AC |
1...n |
The number of a thermostat.
|
| AC parameter |
OnOff, Cool temperature, Mode, Speed, Heat temperature, Auto temperature, Dry temperature. |
Parameters to control a thermostat.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Set the parameters of thermostat |
It sets parameters of a thermostat.
|
| Command |
AC1, AC1 Cool temperature, AC1 Fan speed, AC1 Mode, AC1 Heat temperature, AC1 Auto temperature, Floor Heater, Floor temperature, Floor Heater 1, Floor Heater 2, Floor Heater all. |
Selection of a parameter.
|
| Value* |
On, Off |
AC1
|
| 15 ~ 30 |
AC1 Cool temperature
|
| Auto, High, Med, Low |
AC1 Fan speed
|
| Auto, Cool, Heat, Fan |
AC1 Mode
|
| 15 ~ 35 |
AC1 Heat temperature
|
| 15 ~ 35 |
AC1 Auto temperature
|
| On, Off |
Floor Heater
|
| 15 ~ 35 |
Floor temperature
|
On, Off, Temperature (15 ~ 35) |
Floor Heater 1
|
On, Off, Temperature (15 ~ 35) |
Floor Heater 2
|
On, Off, Temperature (15 ~ 35) |
Floor Heater all
|
| Operation Code |
Read the parameters of thermostat |
It sends a request to get parameters of a thermostat.
|
| Action type |
On/Off |
It gets data about the state of a thermostat (on / off).
|
| Temperature |
It gets the temperature of a thermostat.
|
| Value* |
any value |
It accepts any value to actiavate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Read the temperature unit |
Temperature value.
|
| Value * |
n |
Temperature.
|
| Operation Code |
Read air conditioner Fan speed and Mode En/Dis Flag |
The value of a fan mode.
|
| AC |
1...n |
The number of a conditioner.
|
| Mode |
Fan Auto, Fan Med, Fan Height, Fan Low, Climate Cool, Climate Heat, Climate Fan, Climate Auto, Climate Dry. |
The mode of an air conditioner.
|
| Value * |
0 |
Turned off.
|
| 1 |
Turned on.
|
| Operation Code |
Read air conditioner temperature range |
A temperature range.
|
| AC |
1...n |
The number of an air conditioner.
|
| Temperature parameter |
Cool Low, Cool High, Heat Low, Heat High, Auto Low, Auto High, Dry Low, Dry High. |
Temperature parameter.
|
| Value * |
15-30 |
Cool Low
|
| 15-30 |
Cool High
|
| 15-35 |
Heat Low
|
| 15-35 |
Heat High
|
| 15-35 |
Auto Low
|
| 15-35 |
Auto High
|
| 15-35 |
Dry Low
|
| 15-35 |
Dry High
|
| Operation Code |
Read the parameters of the air condition |
Conditioner parameters.
|
| AC |
1...n |
The number of a conditioner.
|
| AC parameter |
OnOff, Cool temperature, Mode, Speed, Room temperature, Heat temperature, Current mode, Current speed, Auto temperature, Dry temperature. |
Parameters of a conditioners.
|
| Value * |
0 - turned off, 1 - turned on |
OnOff
|
| 15-30 |
Cool temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Mode
|
| 0-3 (Auto, High, Med, Low) |
Speed
|
| 1...n |
Room temperature
|
| 15-35 |
Heat temperature
|
| 0-4 (Cool, Heat, Fan, Auto, Dry) |
Current mode
|
| 0-3 (Auto, High, Med, Low) |
Current speed
|
| 15-35 |
Auto temperature
|
| 15-35 |
Dry temperature
|
| Operation Code |
Parameters of thermostat |
Themostat parameters.
|
| Command |
AC1, AC1 Cool temperature, AC1 Fan speed, AC1 Mode, AC1 Heat temperature, AC1 Auto temperature, Floor Heater, Floor temperature, Floor Heater 1, Floor Heater 2, Floor Heater all. |
Selection of a parameter.
|
| Value* |
1 - On, 0 - Off |
AC1
|
| 15 ~ 30 |
AC1 Cool temperature
|
| 0 ~ 3 (Auto, High, Med, Low) |
AC1 Fan speed
|
| 0 ~ 3 (Auto, Cool, Heat, Fan) |
AC1 Mode
|
| 15 ~ 35 |
AC1 Heat temperature
|
| 15 ~ 35 |
AC1 Auto temperature
|
| 1 - On, 0 - Off |
Floor Heater
|
| 15 ~ 35 |
Floor temperature
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater 1
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater 2
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater all
|
* Value - a value that comes from equipment
Energy
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Energy meter data request |
It requests data from an electricity meter.
|
| Energy type |
Basic, Energy metter data request, This month, (1~12) month energy total |
A type of request.
|
| Value (Energy metter data request) |
Import active, Export active, Import reactive, Export reactive, Total active, Total reactive. |
A type of meter data.
|
| Value (Basic) |
Line to neutral, Current, Active power, Apparent power, Reactive power, Power factor, Phase angle, Frequency. |
A type of meter data.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Energy meter data request |
It requests data from an electricity meter.
|
| Energy type |
Basic, Energy metter data request, This month, (1~12) month energy total |
A type of request.
|
| Value (Energy meter data request) |
Import active, Export active, Import reactive, Export reactive, Total active, Total reactive. |
A type of meter data.
|
| Value (Basic) |
Line to neutral, Current, Active power, Apparent power, Reactive power, Power factor, Phase angle, Frequency. |
A type of meter data.
|
| Value* |
n |
Data from an electricity meter.
|
* Value - a value that comes from equipment
Weather
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read weather status |
It requests weather data
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Read weather status |
It requests data from an electricity meter.
|
| Temperature parameter |
Wind direction, Temperature, Humidity, Wind speed, Gust speed, Rain fall, Lighting intencity, Ultraviolet index, Low battery status, Date time. |
A type of data.
|
| Value* |
1-North, 2-North East, 4-East, 8-South East, 16-South, 32-South West, 64-West, 128-North East. |
Wind direction.
|
| 0 ~ 100 % |
Humidity.
|
| Value |
Wind speed.
|
| Value |
Gust speed.
|
0 - no rain, 1 - rain. |
Rain fall.
|
| Value |
Lighting intencity.
|
| 0 ~ 15 |
Ultraviolet index.
|
0 - normal, 1 - low. |
Low battery status.
|
| date/time on a device. |
Date time.
|
* Value - a value that comes from equipment
Logic 4T sensor / Logic Health sensor / Logic PIR sensor / Logic 10F sensor
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read logic status |
It sends a request to get the status of a device.
|
| Logic ID |
1 ~ n |
Device ID.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Read 10F logic status |
It gets the logic status of 10F.
|
| Logic ID |
1 ~ n |
device ID.
|
| Logic sensor parameter |
Logic delay time, Lux, PIR status, Relay status, Digital input 1-2, FLag A, FLag A status, FLag B, FLag B status, Temperature, Date time, Week. |
Parameters of a logic sensor.
|
| Value* |
n |
Parameter value of a logic sensor.
|
| Operation Code |
Read 4T logic status |
It gets the 4T logic status.
|
| Logic ID |
1 ~ n |
Device ID.
|
| Value* |
n |
Parameter value of a logic sensor.
|
| Operation Code |
Read PIR logic status |
It gets the PIR logic status.
|
| Logic ID |
1 ~ n |
Device ID.
|
| Logic sensor parameter |
Logic delay time, Lux, PIR status, Relay status 1-2, FLag A, FLag A status, FLag B, FLag B status, Date time. |
Parameters of a logic sensor.
|
| Value* |
n |
Parameter value of a logic sensor.
|
| Operation Code |
Read Health logic status |
It gets the Health logic status.
|
| Logic ID |
1 ~ n |
Device ID.
|
| Logic sensor parameter |
Logic delay time, Lux, Noise, Eco, TVOC, Temperature, Humidity, Digital input 1-3, PIR status, FLag A, FLag A status, FLag B, FLag B status, Date time, CO, Eco level, TVOC level, CO level. |
Parameters of a logic sensor.
|
| Value* |
n |
Parameter value of a logic sensor.
|
* Value - a value that comes from equipment
Digital Input
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read Status from 10FEnergy Servant Sensor |
It requests the status of the10FEnergy Servant sensor.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read status from other digital inputs |
It requests the status pf other digital inputs.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Read Status from 10FEnergy Servant Sensor |
It reads the status from the 10FEnergy Servant sensor.
|
| Servant sensor parameter |
Dry contact 1/2, Lux type, Motion sensor, FLAG A/B, Delay time, Lux Value, Type dry contact 1/2. |
Sensor parameters.
|
| Value* |
1 - Closed, 0 - Open. |
Dry contact 1/2
|
| ASCII |
Lux type
|
0 - No motion, 1 - Motion |
Motion sensor
|
0 - Invalid, 1 - Turn off, 2 - Turn on. |
FLAG A/B
|
| 0...n |
Delay time
|
1 - Within the range, 0 - Outside the range |
Lux Value
|
| ASCII |
Type dry contact 1/2
|
| Operation Code |
Read status from other digital inputs |
It reads the status of other digital inputs.
|
| Input no |
1...n |
The number of an input.
|
| Value* |
1 - Opened, 0 - Closed. |
The status of a dry contact.
|
* Value - a value that comes from equipment
Floor Heating
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True / False. |
An interval to send a commad (sec.)
|
| Operation Code |
Read the state of floorheating |
It requests the state of the warm floor.
|
| Id |
FH 1 / FH 2 |
Id of the warm floor.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read the limits of floorheating |
It requests the heating limit of the warm floor.
|
| Id |
FH 1 / FH 2 |
Id of the warm floor.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Controll floorheating |
Control of floor heating.
|
| Id |
FH 1 / FH 2 |
Id of the warm floor.
|
| Command |
Low limit, High limit, Enabled, Mode |
Commands of the warm floor.
|
| Value* |
any value |
Low limit
|
| any value |
High limit
|
0 - Turn off, 1 - Turn ob |
Enabled
|
| 0 ~ n |
Mode
|
| Operation Code |
Set the parameters of thermostat |
Set heating parameters.
|
| Command |
AC1, AC1 Cool temperature, AC1 Fan speed, AC1 Mode, AC1 Heat temperature, AC1 Auto temperature, Floor Heater, Floor temperature, Floor Heater 1/2, Floor Heater all. |
Commands of the warm floor.
|
| Value* |
1 - On, 0 - Off |
AC1
|
| 15 ~ 30 |
AC1 Cool temperature
|
| 0 ~ 3 (Auto, High, Med, Low) |
AC1 Fan speed
|
| 0 ~ 2 (Auto, Cool, Heat) |
AC1 Mode
|
| 15 ~ 35 |
AC1 Heat temperature
|
| 15 ~ 35 |
AC1 Auto temperature
|
| 1 - On, 0 - Off |
Floor Heater
|
| 15 ~ 35 |
Floor temperature
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater 1/2
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater all
|
| Operation Code |
Read the parameters of thermostat |
It requests thermostat parameters.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
State of floorheating |
The state of floor heating.
|
| Id |
FH 1 / FH 2 |
ID of floor heating.
|
| Command |
Room temp, State |
A tracked parameter.
|
| Value* |
0 ~ n |
Room temp
|
1 - Turned on, 0 - Turned off. |
State
|
| Operation Code |
Limits of floorheating |
The limits of floor heating.
|
| Id |
FH 1 / FH 2 |
ID of floor heating.
|
| Command |
Low limit, High limit, Enabled, Mode |
The parameter of limits.
|
| Value* |
any value |
Low limit
|
| any value |
High limit
|
0 - Turned off, 1 - Turned on |
Enabled
|
| 0 ~ n |
Mode
|
| Operation Code |
Parameters of thermostat |
Thermostat parameters.
|
| Command |
AC1, AC1 Cool temperature, AC1 Fan speed, AC1 Mode, AC1 Heat temperature, AC1 Auto temperature, Floor Heater, Floor temperature, Floor Heater 1/2, Floor Heater all. |
Parameters of floor heating.
|
| Value* |
1 - On, 0 - Off |
AC1
|
| 15 ~ 30 |
AC1 Cool temperature
|
| 0 ~ 3 (Auto, High, Med, Low) |
AC1 Fan speed
|
| 0 ~ 2 (Auto, Cool, Heat) |
AC1 Mode
|
| 15 ~ 35 |
AC1 Heat temperature
|
| 15 ~ 35 |
AC1 Auto temperature
|
| 1 - On, 0 - Off |
Floor Heater
|
| 15 ~ 35 |
Floor temperature
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater 1/2
|
1 - On, 0 - Off, Temperature (15 ~ 35) |
Floor Heater all
|
* Value - a value that comes from equipment
10F Energy Servant
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read status from 10FEnergy Servant Sensor |
It requests the status if the 10FEnergy Servant sensor.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read status from other digital inputs |
It requests the status of other digital inputs.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Read status from 10FEnergy Servant Sensor |
It requests the status of the 10FEnergy Servant sensor
|
| Servant sensor parameter |
Dry contact 1/2, Lux type, Motion sensor, FLAG A/B, Delay time, Lux Value, Type dry contact 1/2. |
Sensor parameter
|
| Value* |
Open = 1, Close = 0 |
Dry contact 1/2
|
| 0 ~ n |
Lux type
|
No Movement =0, Movement=1 |
Motion sensor
|
Invalid=0, OFF=1, ON=2 |
FLAG A/B
|
| 0 ~ n (sec) |
Delay time
|
In brightness range=1, Beyond the brightness range=0 |
Lux Value
|
| 0 ~ n |
Type dry contact 1/2
|
| Operation Code |
Read status from other digital inputs |
It requests the status of other diigtal inputs
|
| Input no |
0 ~n |
The number of an input.
|
| Value* |
NC=1, NO=0, Invalid=2 |
Type of dry contact 1/2/3/4
|
Open =1, Close =0. |
Status of dry contact 1/2/3/4
|
* Value - a value that comes from equipment
Security Module
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Arm/Disarm Security |
Activation / deactivation of security devices.
|
| Zone no |
0...n |
The number of a zone.
|
| Command |
Vacation, Away, Night, Night with visitor, Day, Disarm. |
A work mode of devices.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Arm/Disarm Security |
The status of security devices.
|
| Zone no |
0...n |
The number of a zone.
|
| Value* |
1 |
Vacation
|
| 2 |
Away
|
| 3 |
Night
|
| 4 |
Night with visitor
|
| 5 |
Day
|
| 6 |
Disarm
|
* Value - a value that comes from equipment
Universal Switch Project \ Universal Switch DVD \ Universal Switch IPTV \ Universal Switch TV Box \ Universal Switch TV
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.) .
|
| Operation Code |
Universal switch |
Activation of a universal switch.
|
| Switch no |
0...n |
The number of a switch.
|
| Control type |
ON \ Off. |
Turn on \ off
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Universal Switch
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.) .
|
| Operation Code |
Universal switch |
Activation of a universal switch.
|
| Switch no |
0...n |
The number of a switch.
|
| Control type |
ON \ Off. |
Turn on \ off
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Universal switch |
The state of a universal switch
|
| Switch no |
0...n |
The number of a switch.
|
| Value* |
1 |
ON
|
| 0 |
Off
|
* Value - a value that comes from equipment
Curtain Motor
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Read status of curtain |
It sends a request to get the status of the curtain position.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Curtain сontrol |
Activation of a universal switch.
|
| Switch no |
0...n |
The number of a switch.
|
| Control type |
Stop, Open, Close. |
Stop, Open, Close.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Curtain control |
It gets the status of the curtain position.
|
| Switch no |
0...n |
The number of a switch.
|
| Value* |
0 |
Stop
|
| 1 |
Open
|
| 2 |
Close
|
* Value - a value that comes from equipment
Tubular Motor
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Single channel control |
One-channel control.
|
| Channel no |
1~255 (255 is sent to all channels of a device) |
The number of a channel.
|
| Brightness level |
0~100 |
The level of brightness (in per cent).
|
| Dim/ramp time |
0~3600 (сек.) |
The time of activation.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read status of channels |
It gets the staus of channels.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Curtain сontrol |
Control of curtains.
|
| Switch no |
0...n |
The number of a switch.
|
| Control type |
Stop, Open, Close. |
A type of control.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read status of curtain |
It gest the status of the curtain position.
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Single channel control |
It gets the status of channels.
|
| Channel no |
0...n |
The number of a channel.
|
| Value* |
0~100 |
A value in the channel
|
| Operation Code |
Curtain control |
It gest the status of the curtain position.
|
| Switch no |
0...n |
The number of a channel.
|
| Value* |
0 |
Stop
|
| 1 |
Open
|
| 2 |
Close
|
* Value - a value that comes from equipment
RGB \ Dimmer \ Relay
Command:
| Parameter |
Value |
Description
|
| Use Timer |
True, False. |
An interval to send a command (sec.)
|
| Operation Code |
Scene control |
Control of scenes.
|
| Area no |
0~254 |
The number of an area / control zone.
|
| Scene no |
0~254 |
The number of a scene (if the value is 0, the number of the scene will be taken from the Value*)
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Single channel control |
One-channel control
|
| Channel no |
1~255 (255 - it is sent to all channels of a device) |
The number of a channel.
|
| Brightness level |
0~100 |
The brightness level of a selected channel (if the value is 0, the brightness level will be taken from the Value*).
|
| Dim/ramp time |
0~3600 (sec.) |
Time of activation.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Read status of channels |
It requests the status of channels.
|
| Value* |
any value |
It accepts any value to activate a command.
|
| Operation Code |
Sequence Control |
It turns on a sequence of scenes.
|
| Area no |
0~254 |
The number of an area / a control zone.
|
| Sequence no |
0~254 |
The number of a sequence (if the value is, the number of the sequence will be taken from the Value*).
|
| Value* |
any value |
It accepts any value to activate a command.
|
* - enter it when drag'n'dropping a command on a graphic item
Feedback:
| Parameter |
Value |
Description
|
| Operation Code |
Scene control |
It gets the state of channels in a scene.
|
| Area no |
0~254 |
The number of an area / a control zone.
|
| Value* |
0~254 (254 - manuel control, scenes are turned off) |
The current scene (a sequence number).
|
| Operation Code |
Single channel control |
It gets the state of a channel.
|
| Channel no |
1~255 (255 - it is sent to all channels of a device) |
The number of a channel.
|
| Value* |
0~100 |
The current value of a channel.
|
| Operation Code |
Sequence control set status |
The status of a set of sequence of scenes.
|
| Area no |
0~254 |
The number of an area / a control zone.
|
| Value* |
0~254 |
The current status.
|
* Value - a value that comes from equipment